Skip to main content
Your Saved For Later list is empty.
My Favorites

Blazecut T Series - T200E Automatic Fire Suppression System

Item #: BZT-T200E
There are no reviews yet Write a review
Price: $530.69 inc GST
Retail Price: ##RETAILPRICE## inc GST
    Points to Purchase:3538
    The product is in stock Availability: Stocked(Local Warehouse)
    Usually ships In a day

    About This Item

    • Compact & Versatile: BlazeCut Tube protects A, B, C, and electrical fires with no cylinder required, fitting inside enclosures.
    • Automatic & Independent: Heat‑sensitive tube activates at high temperatures, operates 24/7 without power, and requires zero maintenance.
    • Safe & Effective: Uses globally accepted HFC‑227ea agent, harmless to people and equipment, with long service life up to 10 years.
    • Simple Installation & Monitoring: Easy to secure with cable ties/clamps, includes pressure gauge and optional switch for added safety functions.
    Featured

    Blazecut T Series - T200E Automatic Fire Suppression System

    BlazeCut T Series system are our advanced self contained tubular style systems that are cylinder-less and easy to install. The BlazeCut T series system is conveniently supplied in a retail box ready t

    Blazecut T Series - T200E Automatic Fire Suppression System
    BLAZECUT T

    Blazecut T Series - T200E Automatic Fire Suppression System

    BlazeCut T Series system are our advanced self contained tubular style systems that are cylinder-less and easy to install. The BlazeCut T series system is conveniently supplied in a retail box ready to display in a shop front or just easy transport. The retail package comes with the T series system, user manual, heavy duty cable ties and warning labels.

    CLEAN EXTINGUISHING

    Clean Extinguishing Agent

    HFC-227ea clean extinguishing agent is a liquefied gas used for volume fire suppression. HFC clean extinguishing agent is discharged as a stream of gas and liquid droplets that penetrate into the fire area, ceasing the combustion process through heat absorption and a chemical interaction. HFC clean extinguishing agent is considered environmentally accepted substitute for Halon extinguishing agents used in the past, which are harmful to the ozone layer.

    BlazeCut T Series system uses liquefied gas, HFC-227ea fire extinguishing agent. The extinguishing agent is a world- wide known and accepted gaseous clean agent used for total flooding fire suppression applications with very high effectivity, zero ozone depletion potential and safe to people. It is the agent of choice for protection of enclosure

    AUTOMOTIVE AND MOBILE

    Automotive and Mobile Machinery

    Vehicle fires are an issue all over the world and the number of such fires increases each year. Majority of vehicle fires have its source in the engine compartment. The most dangerous sources of fires in the engine compartments include electrical arcing, overloaded wiring, hot surfaces, mechanical sparks, electrical sources. The engine compartments of vehicles are one of the most critical environments due to the increased risk of fire and in terms of extinguishing. Tight space, hot environment, changing temperatures, and air flow have substantial impact on extinguishing and pose a challenge for every fire suppression system. BlazeCut “T” Series systems help protect engine compartments by capturing the staring fire or by suppressing the fire giving the crew time for further action. Easy installation, no maintenance and affordability makes this system a perfect first line fire protection of the engine compartment of small vehicles and pleasure boats. BlazeCut “T” Series systems with integreated pressure switch, add "S" as suffix when ordering. eg. TxxxES

    Automotive and Mobile Machinery
    3D PRINTERS

    3D Printers

    Home hobbyists are becoming more and more popular and many owners never consider the fire risks or consequences of not being adequately equipped should a fire occur. Fires can start small but can quickly escalate and major loss of property or even life can occur.

    3D printers and laser cutters can be left unattended so having an automatic system should be a basic consideration to avoid any accidents with the equipment. Despite being present in such a situation, at such a distressful time many end up not recalling the imminent danger of opening a hood during fire and the risk of the fire flaring up and burning them is extremely high.

    Sizing and Selection

    Applications can be calculated by a simple process, measure the sealed enclosures Width x Height x Depth in metres or feet and this will calculate your required volume in m3 or ft3. Then refer to the chart below for the maximum volume protected for electrical or engine applications to select the suitable T Series model. Note: the enclosure should be enclosed or have minimal ventilation. The T Series system is not suitable for open areas. For vehicle applications please refer to our application guide that can be found online at www.blazecut.com

    Model* Electrical Fires**
    @ 20°C (68°F)
    Engine Fires**
    @ 20°C (68°F)
    Amount of Agent System Length Operation Temperature Activation Temperature
    T025E 0.09 m³ / 3.18 ft³ 0.09 m³ / 3.18 ft³ 0.05 kg ± 2 g / 0.11 lb ± 0.07 oz 28 cm / 11.02 in

    -40°C to +90°C / -40°F to 194°F

    105°C ± 3°C / 221°F ± 37°F
    T050E 0.18 m³ / 6.36 ft³ 0.14 m³ / 4.94 ft³ 0.10 kg ± 2 g / 0.22 lb ± 0.07 oz 53 cm / 20.87 in

    -40°C to +90°C / -40°F to 194°F

    105°C ± 3°C / 221°F ± 37°F
    T100E 0.46 m³ / 16.24 ft³ 0.35 m³ / 12.36 ft³ 0.25 kg ± 5 g / 0.55 lb ± 0.17 oz 113 cm / 44.48 in

    -40°C to +90°C / -40°F to 194°F

    105°C ± 3°C / 221°F ± 37°F
    T200E 0.91 m³ / 32.14 ft³ 0.69 m³ / 24.37 ft³ 0.50 kg ± 5 g / 1.10 lb ± 0.17 oz 215 cm / 84.64 in -40°C to +90°C / -40°F to 194°F 105°C ± 3°C / 221°F ± 37°F
    T300E 1.37 m³ / 48.38 ft³ 1.04 m³ / 36.73 ft³ 0.75 kg ± 10 g / 1.65 lb ± 0.35 oz 319 cm / 125.59 in

    -40°C to +90°C / -40°F to 194°F

    105°C ± 3°C / 221°F ± 37°F
    T400E 1.82 m³ / 64.27 ft³ 1.39 m³ / 49.09 ft³ 1.00 kg ± 10 g / 2.20 lb ± 0.35 oz 422 cm / 166.14 in

    -40°C to +90°C / -40°F to 194°F

    105°C ± 3°C / 221°F ± 37°F

    T500E 2.28 m³ / 80.52 ft³ 1.73 m³ / 61.09 ft³ 1.25 kg ± 10 g / 2.76 lb ± 0.35 oz 526 cm / 207.09 in -40°C to +90°C / -40°F to 194°F

    105°C ± 3°C / 221°F ± 37°F

    T600E 2.73 m³ / 96.41 ft³ 2.08 m³ / 73.45 ft³ 1.50 kg ± 10 g / 3.31 lb ± 0.35 oz 630 cm / 248.03 in -40°C to +90°C / -40°F to 194°F

    105°C ± 3°C / 221°F ± 37°F

    T025ES 0.09 m³ / 3.18 ft³ 0.09 m³ / 3.18 ft³ 0.05 kg ± 2 g / 0.11 lb ± 0.07 oz 35 cm / 13.78 in
    -20°C to +80°C / -4°F to 176°F
    100°C ± 2°C / 212°F ± 36°F
    T050ES 0.18 m³ / 6.36 ft³ 0.14 m³ / 4.94 ft³ 0.10 kg ± 2 g / 0.22 lb ± 0.07 oz 60 cm / 23.62 in -20°C to +80°C / -4°F to 176°F
    100°C ± 2°C / 212°F ± 36°F
    T100ES 0.46 m³ / 16.24 ft³ 0.35 m³ / 12.36 ft³ 0.25 kg ± 5 g / 0.55 lb ± 0.17 oz 120 cm / 47.24 in -20°C to +80°C / -4°F to 176°F
    100°C ± 2°C / 212°F ± 36°F
    T200ES 0.91 m³ / 32.14 ft³ 0.69 m³ / 24.37 ft³ 0.50 kg ± 5 g / 1.10 lb ± 0.17 oz 222 cm / 87.40 in -20°C to +80°C / -4°F to 176°F 100°C ± 2°C / 212°F ± 36°F
    T300ES 1.37 m³ / 48.38 ft³ 1.04 m³ / 36.73 ft³ 0.75 kg ± 10 g / 1.65 lb ± 0.35 oz 326 cm / 128.34 in -20°C to +80°C / -4°F to 176°F
    100°C ± 2°C / 212°F ± 36°F
    T400ES 1.82 m³ / 64.27 ft³ 1.39 m³ / 49.09 ft³ 1.00 kg ± 10 g / 2.20 lb ± 0.35 oz 429 cm / 168.89 in -20°C to +80°C / -4°F to 176°F
    100°C ± 2°C / 212°F ± 36°F
    T500ES 2.28 m³ / 80.52 ft³ 1.73 m³ / 61.09 ft³ 1.25 kg ± 10 g / 2.76 lb ± 0.35 oz 533 cm / 209.84 in -20°C to +80°C / -4°F to 176°F
    100°C ± 2°C / 212°F ± 36°F
    T600ES 2.73 m³ / 96.41 ft³ 2.08 m³ / 73.45 ft³ 1.50 kg ± 10 g / 3.31 lb ± 0.35 oz 637 cm / 250.79 in -20°C to +80°C / -4°F to 176°F
    100°C ± 2°C / 212°F ± 36°F

    *Letter “S” in model designation stands for an integrated pressure switch that allows connection of a signaling device of to perform a shutdown operation at time of agent discharge. TxxxE does not require power.

    ** Calculated design concentration 7% (Electrical Fires) and 9% (Engine Fires) and an ambient temperature of 20°C (68°F) for the enclosure. Please note if a lower temperature is present the coverage potential will be reduced, please contact your local BlazeCut agent for further information.

    • Blazecut T Series Automatic Fire Suppression *1
    • Nylon Straps
    • Stickers